Why Cooling Systems Are Needed
During normal operation, water returning from the data center enters the air coolers at approximately 90°F and is cooled to approximately 70°F before being delivered back to the facility.
If the air coolers fail, that temperature reduction stops. Without stored cooling capacity, approximately 90°F water could begin flowing directly back toward the data center.
The Cimarron Thermal Energy Storage Tank creates a buffer between the air coolers and the data center. Its stored mass of chilled water continues supplying approximately 70°F water for a defined period while the cooling system is restored.
For the initial application, the vessel is engineered to provide approximately five minutes of thermal ride-through before the warmer water reaches the bottom outlet.